Detect Danfoss AK-SM 800A Series Improper Authentication (CVE-2025-41450) in IBM QRadar
Detects exploitation attempts against the improper authentication vulnerability (CWE-305: Authentication Bypass by Primary Weakness) in Danfoss AK-SM 800A Series refrigeration/HVAC system managers running firmware < 4.2. The flaw allows a remote, unauthenticated attacker to bypass authentication on the web management interface, gaining administrative access to the OT device. CISA KEV-listed. Detection focuses on anomalous HTTP access to the AK-SM web UI, successful authentication without a preceding credential exchange, access from untrusted networks to a device that should be segmented, and the request patterns associated with the public 'fromagegate' PoC.
MITRE ATT&CK
- Tactic
- Initial Access Credential Access
QRadar Detection Query
-- df00tech DF00-155935072d · https://df00tech.com/detections/CVE-2025-41450 · licence: https://df00tech.com/detections/licence
SELECT sourceip, destinationip, "URL" AS url, COUNT(*) AS request_count
FROM events
WHERE destinationport IN (80, 443, 8080)
AND ("URL" ILIKE '%/login%' OR "URL" ILIKE '%/cgi-bin%' OR "URL" ILIKE '%/menu%' OR "URL" ILIKE '%/edf%' OR "URL" ILIKE '%/datapoint%')
AND INCIDR('0.0.0.0/0', sourceip) = true
AND INCIDR('10.0.0.0/8', sourceip) = false
AND INCIDR('172.16.0.0/12', sourceip) = false
AND INCIDR('192.168.0.0/16', sourceip) = false
GROUP BY sourceip, destinationip, url
HAVING request_count > 5
LAST 24 HOURS QRadar AQL detecting external access to Danfoss AK-SM 800A web endpoints indicative of CVE-2025-41450 auth bypass.
Data Sources
Required Tables
False Positives & Tuning
- Scanner activity
- Authorized vendor maintenance
- NAT-masked internal maintenance traffic
Other platforms for CVE-2025-41450
Testing Methodology
Validate this detection against 3 adversary techniques from Atomic Red Team. Each test below lists the behaviour to exercise and the telemetry you should expect to see. Executable commands and cleanup steps are further down this page.
- Test 1 Simulated unauthenticated access to AK-SM login path
Expected signal: Firewall/proxy HTTP log entry showing source IP accessing /login on the AK-SM device port
- Test 2 Burst of management-path requests simulating PoC enumeration
Expected signal: Multiple HTTP requests to AK-SM paths from a single source within a short window
- Test 3 External-source probe of AK-SM interface
Expected signal: HTTP connection log from an external/non-private source to the AK-SM device
References (4)
Response Playbook
Triage
- Confirm the destination IP is a Danfoss AK-SM 800A device and identify its firmware version; versions < 4.2 are vulnerable to CVE-2025-41450.
- Review whether the source IP is an authorized maintenance host or an untrusted external address; correlate with any approved change/maintenance window.
- Inspect the full HTTP request/response sequence for a successful session established without a valid credential exchange (authentication bypass signature).
- Check whether the AK-SM device should be internet- or corporate-reachable at all; OT devices are expected to be segmented.
Containment
- Block the offending source IP at the perimeter/OT firewall and restrict the AK-SM management interface to an isolated OT management VLAN.
- If compromise is suspected, take the AK-SM web interface offline or place the device behind an ACL permitting only known maintenance hosts until firmware is upgraded to >= 4.2.
Evidence Collection
- Export firewall/proxy logs showing the source IP, destination AK-SM IP, URLs, and timestamps of the suspicious session.
- Capture the AK-SM device audit/access logs and current configuration (set points, user accounts, scheduled actions) to detect unauthorized changes to refrigeration/HVAC parameters.
Escalation Criteria
- !Escalate to OT/ICS incident response and management if administrative access was achieved or device configuration (alarms, setpoints, accounts) was modified.
- !Escalate to physical-safety and facilities teams if refrigeration control changes could affect food safety, cold-chain integrity, or life-safety systems.
Investigation Guide
Forensic Artifacts
- >
AK-SM web server access/audit logs - >
Firewall and proxy connection logs for the OT segment - >
Device configuration snapshots (user accounts, setpoints, alarm thresholds)
Tuning Guidance
Maintain an inventory list of AK-SM 800A device IPs and populate the empty host arrays in the queries. Allow-list authorized maintenance/integrator source IPs and sanctioned vulnerability scanners to reduce noise. Tune the request-count threshold to your environment's normal management activity, and prioritize alerts where the source is external and no change window is active.
Hunting Queries
Baseline and surface all clients contacting AK-SM management ports to find unexpected sources.
// df00tech DF00-155935072d · https://df00tech.com/detections/CVE-2025-41450 · licence: https://df00tech.com/detections/licence
CommonSecurityLog | where DeviceCustomString1 has "AK-SM" or DestinationIP in (dynamic([])) | where DestinationPort in (80,443,8080) | summarize count() by SourceIP, DestinationIP, bin(TimeGenerated, 1h) | order by count_ desc ``` df00tech DF00-155935072d · https://df00tech.com/detections/CVE-2025-41450 · licence: https://df00tech.com/detections/licence ```
index=network (dest_port=80 OR dest_port=443 OR dest_port=8080) dest_ip IN (<ak_sm_ips>) | stats count values(url) by src_ip dest_ip | sort - count Atomic Red Team Tests
Issues an HTTP request to the AK-SM web UI login path from an unauthorized host to generate detection telemetry (lab only).
Command
curl -sk -o /dev/null -w "%{http_code}\n" https://ak-sm-lab.internal/login Cleanup
echo 'No cleanup required; stateless HTTP GET' Expected Telemetry
Firewall/proxy HTTP log entry showing source IP accessing /login on the AK-SM device port
Expected Detection
KQL/SPL rules flag external access to AK-SM management path
Sends repeated requests to multiple AK-SM endpoints to mimic the fromagegate PoC enumeration pattern (lab only).
Command
for p in /login /cgi-bin /menu /edf /datapoint /api; do curl -sk -o /dev/null https://ak-sm-lab.internal$p; done Cleanup
echo 'No cleanup required' Expected Telemetry
Multiple HTTP requests to AK-SM paths from a single source within a short window
Expected Detection
Rules trigger when request_count exceeds the configured threshold
From a host outside the OT segment, probe the AK-SM device to validate the non-RFC1918 source logic.
Command
powershell -Command "try { Invoke-WebRequest -UseBasicParsing -Uri 'https://ak-sm-lab.internal/datapoint' -SkipCertificateCheck } catch {}" Cleanup
echo 'No cleanup required' Expected Telemetry
HTTP connection log from an external/non-private source to the AK-SM device
Expected Detection
Detection fires on external source accessing AK-SM management endpoint